| Circuit breaker size S3 For starter combination Rated current 20 A Short-circuit release 260 A Screw terminal Increased switching capacity !!! Phased-out product !!! Successor is SIRIUS 3RV2 Preferred successor type is >>3RV2332-4BC10<< |
Product brand name | SIRIUS |
Product designation | circuit breaker |
Design of the product | for starter combinations |
General technical data |
Product extension | |
Auxiliary switch | Yes |
Power loss [W] total typical | 20 W |
Surge voltage resistance rated value | 6 000 V |
Protection class IP | |
on the front | IP20 |
Shock resistance | 25g / 11 ms |
Mechanical service life (switching cycles) | |
of the main contacts typical | 50 000 |
Continuous current rated value | 20 A |
Ambient conditions |
Installation altitude at height above sea level | |
maximum | 2 000 m |
Ambient temperature | |
during operation | -20 ... +60 °C |
during storage | -50 ... +80 °C |
during transport | -50 ... +80 °C |
Main circuit |
Number of poles for main current circuit | 3 |
Operating voltage | |
rated value | 690 V |
at AC-3 rated value maximum | 690 V |
Operating current | |
at AC-3 | |
— at 400 V rated value | 20 A |
Operating power | |
at AC-3 | |
— at 400 V rated value | 7.5 kW |
Operating frequency | |
at AC-3 maximum | 15 1/h |
Auxiliary circuit |
Number of CO contacts | |
for auxiliary contacts | 0 |
Protective and monitoring functions |
Product function | |
Ground fault detection | No |
Phase failure detection | No |
Maximum short-circuit current breaking capacity (Icu) | |
at AC at 240 V rated value | 100 kA |
at AC at 400 V rated value | 100 kA |
at AC at 500 V rated value | 30 kA |
at AC at 690 V rated value | 12 kA |
Short-circuit protection |
Design of the overcurrent release and short-circuit release | magnetic |
Installation/ mounting/ dimensions |
Mounting position | any |
Mounting type | screw and snap-on mounting onto 35 mm standard mounting rail according to DIN EN 50022 |
Height | 165 mm |
Width | 70 mm |
Depth | 174 mm |
Required spacing | |
with side-by-side mounting | |
— Backwards | 0 mm |
— at the side | 0 mm |
Connections/Terminals |
Product function | |
removable terminal for auxiliary and control circuit | No |
Type of electrical connection | |
for main current circuit | screw-type terminals with box terminals |
for auxiliary and control current circuit | screw-type terminals |
Arrangement of electrical connectors for main current circuit | front side |
Type of connectable conductor cross-sections | |
for main contacts | |
— solid | 2x (2.5 ... 16 mm²) |
— stranded | 2x (10 ... 50 mm²), 1x (10 ... 70 mm²) |
— finely stranded with core end processing | 2x (2.5 ... 35 mm²), 2.5 ... 50 mm² |