6DL1155-6AU00-0PM0
ET 200SP HA, IM155-6 PN

From SIEMENS

SIMATIC ET 200SP HA, PROFINET interface module IM155-6 PN max. 56 I/O modules, multi-hot swap, without server module
General information
Product type designationIM 155-6 PN
HW functional statusFS03
Firmware versionV1.1
Vendor identification (VendorID)02AH
Device identifier (DeviceID)030FH
Product function
I&M dataYes; I&M0 to I&M3
Engineering with
PCS 7 configurable/integrated as of versionV9.0
Configuration control
via datasetNo
Supply voltage
Rated value (DC)24 V
permissible range, lower limit (DC)19.2 V
permissible range, upper limit (DC)28.8 V
Reverse polarity protectionYes
Short-circuit protectionYes
Mains buffering
Mains/voltage failure stored energy time10 ms
Input current
Current consumption, max.700 mA; +19.2 V to +28.8 V DC
Inrush current, max.5 A
I²t0.36 A²·s; Due to increased mains buffering of 10 ms
Power
Infeed power to the backplane bus7.5 W; No doubling in redundant mode as the infeed power is also designed as redundant.
Power loss
Power loss, typ.2.4 W
Address area
Address space per module
Address space per module, max.256 byte
Address space per station
Address space per station, max.1 440 byte; 1 440 bytes R1 and S1 without CiR, otherwise 1 000 bytes
Hardware configuration
Integrated power supplyYes; 24 V DC
Rack
Modules per rack, max.56; 56 slots for I/O modules + server module (width without IM ≤ 1.3 m)
Time stamping
Accuracy1 ms; In compliance with the supplementary conditions described in the Equipment Manual
Interfaces
Number of PROFINET interfaces1; 2 ports (switch)
1. Interface
Interface types
Number of ports2; via BusAdapter
integrated switchYes
BusAdapter (PROFINET)Yes; Compatible BusAdapters: BA 2x RJ45, BA 2x FC, BA 2x LC, BA LC/RJ45, BA LC/FC, BA VD
Protocols
PROFINET IO DeviceYes
Open IE communicationYes
Media redundancyYes; as MRP client
Interface types
RJ 45 (Ethernet)
Transmission procedurePROFINET with 100 Mbit/s full duplex (100BASE-TX)
100 MbpsYes; PROFINET with 100 Mbit/s full duplex (100BASE-TX)
AutonegotiationYes
AutocrossingYes
Protocols
PROFINET IO Device
Services
— Open IE communicationYes
Redundancy mode
MRPYes
PROFINET system redundancy (S2)Yes; S2, R1
Open IE communication
TCP/IPYes
SNMPYes
LLDPYes
Interrupts/diagnostics/status information
Status indicatorYes
AlarmsYes
Diagnostics functionYes
Diagnostics indication LED
RUN LEDYes; Green LED
ERROR LEDYes; Red LED
MAINT LEDYes; yellow LED
ACTIVE-LED (active IM in redundant configuration)Yes; Green LED
Monitoring of the supply voltage (PWR-LED)Yes; green PWR LED
Connection display LINK TX/RXYes; 2x green link LEDs on BusAdapter
Potential separation
between PROFINET and all other circuitsYes; 1500 V AC
between supply and all other circuitsYes; Type tested with 1 500 V DC
Permissible potential difference
between different circuitsSafety extra low voltage SELV
Isolation
Isolation tested with1 500 V DC/1 min, type test
Ambient conditions
Ambient temperature during operation
horizontal installation, min.-40 °C
horizontal installation, max.70 °C
vertical installation, min.-40 °C
vertical installation, max.60 °C
Dimensions
Width50 mm
Height138 mm
Depth89 mm
Weights
Weight, approx.192 g; without BusAdapter
last modified:03/12/2019