6ES7417-4HL04-0AB0
CPU 417H, 4 IF, 20MB, F. S7-400H

From SIEMENS

SIMATIC S7-400H, CPU 417H Central processing unit for S7-400H 4 interfaces: 1 MPI/DP, 1 DP and 2 for sync modules 20 MB memory (10 MB data/10 MB program)
General information
Product type designationCPU 417H
Supply voltage
Rated value (DC)
24 V DCYes
Input current
from backplane bus 5 V DC, max.1.7 A
Power loss
Power loss, typ.6 W
Memory
Work memory
integrated20 Mbyte
expandableNo
Load memory
expandable FEPROMYes; with Memory Card (FLASH)
expandable FEPROM, max.64 Mbyte
integrated RAM, max.256 kbyte
expandable RAMYes; with Memory Card (RAM)
expandable RAM, max.64 Mbyte
Backup
presentYes
with batteryYes; all data
without batteryNo
Battery
Backup battery
Backup current, typ.600 µA
Backup current, max.1 810 µA
Feeding of external backup voltage to CPU5 V DC to 15 V DC
CPU processing times
for bit operations, typ.0.03 µs
for word operations, typ.0.03 µs
for fixed point arithmetic, typ.0.03 µs
for floating point arithmetic, typ.0.09 µs
CPU-blocks
DB
Number, max.8 192; DB 0 reserved
Size, max.64 kbyte
FB
Number, max.6 144
Size, max.64 kbyte
FC
Number, max.6 144
Size, max.64 kbyte
OB
Number, max.see instruction list
Size, max.64 kbyte
Nesting depth
per priority class24
additional within an error OB2
Counters, timers and their retentivity
S7 counter
Number2 048
Retentivity
— adjustableYes
— lower limit0
— upper limit2 047
— presetZ 0 to Z 7
Counting range
— lower limit1
— upper limit999
IEC counter
presentYes
TypeSFB
S7 times
Number2 048
Time range
— lower limit10 ms
— upper limit9 990 s
IEC timer
presentYes
TypeSFB
Data areas and their retentivity
Flag
Number, max.16 kbyte
Retentivity availableYes; MB 0 to MB 16383
Retentivity presetMB 0 to MB 15
Address area
I/O address area
Inputs16 kbyte
Outputs16 kbyte
Process image
Inputs, adjustable16 kbyte
Outputs, adjustable16 kbyte
Inputs, default1 024 byte
Outputs, default1 024 byte
Subprocess images
Number of subprocess images, max.8
Digital channels
Inputs131 072
— of which central131 072
Outputs131 072
— of which central131 072
Analog channels
Inputs8 192
— of which central8 192
Outputs8 192
— of which central8 192
Hardware configuration
Number of expansion units, max.21
MulticomputingNo
Interface modules
Number of connectable IMs (total), max.6
Number of connectable IM 460s, max.6
Number of connectable IM 463s, max.6; IM 463-2
Number of DP masters
integrated2
via CP10
via IM 4670
Mixed mode IM + CP permittedNo; IM 467 cannot be used jointly with CP 443-5 Ext.
via interface module0
Number of operable FMs and CPs (recommended)
FM64; Limited by number of slots and number of connections
CP, PtP64; Limited by number of slots and number of connections
CP, LAN64; Limited by number of slots and number of connections
Slots
required slots2
Time of day
Clock
Hardware clock (real-time)Yes
retentive and synchronizableYes
Operating hours counter
Number8
Clock synchronization
supportedYes
1. Interface
PhysicsRS 485 / PROFIBUS
IsolatedYes
Protocols
MPIYes; Default setting
PROFIBUS DP masterYes
PROFIBUS DP slaveNo
MPI
Number of connections44
Transmission rate, max.12 Mbit/s
Services
— PG/OP communicationYes
— Global data communicationNo
— S7 basic communicationNo
— S7 communicationYes
— S7 communication, as clientYes
— S7 communication, as serverYes
PROFIBUS DP master
Number of connections, max.32
Transmission rate, max.12 Mbit/s
Number of DP slaves, max.32; Number of slots, max. 512
Services
— PG/OP communicationYes
— Global data communicationNo
— S7 basic communicationNo
— S7 communicationNo
— S7 communication, as clientNo
— S7 communication, as serverNo
— EquidistanceNo
— SYNC/FREEZENo
— Activation/deactivation of DP slavesNo
— Direct data exchange (slave-to-slave communication)No
Address area
— Inputs, max.2 kbyte
— Outputs, max.2 kbyte
User data per DP slave
— Inputs, max.244 byte
— Outputs, max.244 byte
2. Interface
PhysicsRS 485 / PROFIBUS
IsolatedYes
Protocols
PROFIBUS DP masterYes
PROFIBUS DP slaveNo
Point-to-point connectionNo
PROFIBUS DP master
Number of connections, max.32
Transmission rate, max.12 Mbit/s
Number of DP slaves, max.125; Number of slots, max. 2048
Services
— PG/OP communicationYes
— Global data communicationNo
— S7 basic communicationNo
— S7 communicationNo
— S7 communication, as clientNo
— S7 communication, as serverNo
— EquidistanceNo
— SYNC/FREEZENo
— Activation/deactivation of DP slavesNo
— Direct data exchange (slave-to-slave communication)No
Address area
— Inputs, max.8 kbyte
— Outputs, max.8 kbyte
User data per DP slave
— Inputs, max.244 byte
— Outputs, max.244 byte
Communication functions
PG/OP communicationYes
Global data communication
supportedNo
S7 basic communication
supportedNo
S7 communication
supportedYes
as serverYes
as clientYes
User data per job, max.64 kbyte
S5 compatible communication
supportedYes; via CP and loadable FC
User data per job, max.8 kbyte
Standard communication (FMS)
supportedYes; Via CP and loadable FB
User data per job, max.Dependent on CP
Number of connections
overall64
usable for PG communication
— reserved for PG communication1
— adjustable for PG communication, max.0
usable for OP communication
— reserved for OP communication1
— adjustable for OP communication, max.0
usable for S7 basic communication
— reserved for S7 basic communication0
— adjustable for S7 basic communication, max.0
usable for routing
— reserved for routing0
— adjustable for routing, max.0
S7 message functions
Number of login stations for message functions, max.16
Configuration
Configuration software
STEP 7Yes; V5.0 SP2
Programming
Programming language
— LADYes
— FBDYes
— STLYes
— SCLYes
— CFCYes
— GRAPHYes
— HiGraph®Yes
Know-how protection
User program protection/password protectionYes
Dimensions
Width50 mm
Height290 mm
Depth219 mm
Weights
Weight, approx.1 070 g
last modified:03/13/2019