| SIMATIC Compact Field Unit PA Edition with 16x I/O channels PROFINET interface V2.3 (RT) Use of PROFINET bus adapter Media redundancy (MRP) PROFINET system redundancy (S2) Configuration in Run (CiR) Process interfaces: 8x PROFIBUS PA and 8x freely configurable DIQ Installation up to hazardous zone 2 Temperature range -40 to +70 °C Conformal coating Mounting on 35 mm standard mounting rail |
General information |
Product type designation | Compact Field Unit |
HW functional status | E01 |
Firmware version | V1.0 |
FW update possible | Yes |
Vendor identification (VendorID) | 002AH |
Device identifier (DeviceID) | 060DH |
Number of channels | 16 |
Product function |
I&M data | Yes; I&M0 to I&M4 |
The user can configure digital channels as input/output as required | Yes |
Digital channels can be parameterized | Yes |
Engineering with |
STEP 7 TIA Portal configurable/integrated as of version | - / - |
STEP 7 configurable/integrated as of version | From STEP 7 V5.6 HF1 and higher |
PCS 7 configurable/integrated as of version | V9.0 |
PROFIBUS as of GSD version/GSD revision | - / - |
Installation type/mounting |
Mounting | on 35 mm DIN rail, 2 spacing units wide |
Mounting position | Horizontal, vertical |
Supply voltage |
Type of supply voltage | 24 V DC |
Rated value (DC) | 24 V |
permissible range, lower limit (DC) | 19.2 V |
permissible range, upper limit (DC) | 28.8 V |
Reverse polarity protection | Yes |
Short-circuit protection | Yes |
Redundant power supply | Yes |
Mains buffering |
Mains/voltage failure stored energy time | 5 ms; Bridging for field devices and communication |
Input current |
Current consumption (rated value) | 2.5 A |
Current consumption, max. | 2.55 A |
Inrush current, max. | 8 A |
I²t | 0.3 A²·s |
Encoder supply |
Number of outputs | 8 |
Output voltage encoder supply, min. | 18.2 V |
Short-circuit protection | Yes; Electronic |
Output current |
up to 60 °C, max. | 2 A |
up to 70 °C, max. | 1 A |
Power loss |
Power loss, typ. | 8.2 W; Depending on the type of BusAdapter used (typ. RJ45) |
Address area |
Address space per station |
Address space per station, max. | 1 440 byte; Dependent on configuration |
Digital inputs |
Number of digital inputs | 8 |
Source/sink input | Yes; P-reading |
Input characteristic curve in accordance with IEC 61131, type 1 | Yes |
Input characteristic curve in accordance with IEC 61131, type 2 | No |
Input characteristic curve in accordance with IEC 61131, type 3 | Yes |
Pulse extension | No |
Number of simultaneously controllable inputs |
horizontal installation |
— up to 60 °C, max. | 8; Total current must be observed, see DQ |
— up to 70 °C, max. | 8; Total current must be observed, see DQ |
vertical installation |
— up to 60 °C, max. | 8; Total current must be observed, see DQ |
Input voltage |
Rated value (DC) | 24 V |
for signal "0" | -30 to +5V |
for signal "1" | +11 to +30V |
Input current |
for signal "1", typ. | 2.5 mA; Typical |
Input delay (for rated value of input voltage) |
for standard inputs |
— parameterizable | No |
— at "0" to "1", max. | 3.2 ms |
— at "1" to "0", max. | 3.2 ms |
Cable length |
shielded, max. | 1 000 m |
unshielded, max. | 600 m |
Digital outputs |
Type of digital output | Transistor |
Number of digital outputs | 8 |
Current-sinking | No |
Current-sourcing | Yes |
Short-circuit protection | Yes |
Response threshold, typ. | 0.7 to 1.3 A |
Limitation of inductive shutdown voltage to | Typ. L+ (-50 V) |
Controlling a digital input | Yes |
Switching capacity of the outputs |
on lamp load, max. | 5 W |
Load resistance range |
lower limit | 48 Ω |
upper limit | 12 kΩ |
Output voltage |
Type of output voltage | DC |
for signal "1", min. | Ue minus 1 V |
Output current |
for signal "1" rated value | 0.5 A |
for signal "0" residual current, max. | 0.1 mA |
Output delay with resistive load |
"0" to "1", max. | 50 µs |
"1" to "0", max. | 100 µs |
Parallel switching of two outputs |
for uprating | No |
for redundant control of a load | No |
Switching frequency |
with resistive load, max. | 100 Hz |
with inductive load, max. | 2 Hz |
on lamp load, max. | 10 Hz |
Total current of the outputs |
Current per channel, max. | 0.5 A |
horizontal installation |
— up to 60 °C, max. | 2 A |
— up to 70 °C, max. | 1 A |
vertical installation |
— up to 60 °C, max. | 2 A |
Cable length |
shielded, max. | 1 000 m |
unshielded, max. | 600 m |
Encoder |
Connectable encoders |
2-wire sensor | Yes |
— permissible quiescent current (2-wire sensor), max. | 1.5 mA |
Interfaces |
Number of PROFINET interfaces | 1 |
Number of PROFIBUS interfaces | 0 |
PROFIBUS PA |
Transmission rate, max. | 31.25 kbit/s |
Number of connectable PA field devices | 8; Electrically isolated from other interfaces, isolation tested at 2 500 V DC |
Current output to PA field devices, max. | 320 mA |
permissible current per spur line | 40 mA |
Automatic addressing | Yes |
System-supported integration of field devices via PA profiles | Yes |
Extended fieldbus diagnostics | Yes |
1. Interface |
Interface type | PROFINET |
Isolated | Yes |
Interface types |
Number of ports | 2 |
integrated switch | Yes |
BusAdapter (PROFINET) | Yes |
Protocols |
PROFINET IO Device | Yes |
PROFIBUS DP slave | No |
Interface types |
RJ 45 (Ethernet) |
100 Mbps | Yes |
Autonegotiation | Yes |
Autocrossing | Yes |
Protocols |
Supports protocol for PROFINET IO | Yes |
Redundancy mode |
MRP | Yes |
PROFINET system redundancy (S2) | Yes; Type S2 |
Open IE communication |
LLDP | Yes |
Isochronous mode |
Isochronous operation (application synchronized up to terminal) | No |
Interrupts/diagnostics/status information |
Status indicator | Yes |
Alarms | Yes |
Diagnostics function | Yes |
Diagnostic messages |
Monitoring of encoder power supply | Yes |
Wire-break | Yes |
Short-circuit | Yes |
Diagnostics indication LED |
RUN LED | Yes; Green LED |
ERROR LED | Yes; Red LED |
MAINT LED | Yes; yellow LED |
Monitoring of the supply voltage (PWR-LED) | Yes |
Digital input status indicator | Yes |
Digital output status indicator | Yes |
Spur line status/fault | Yes |
Potential separation |
between the channels and PROFINET | Yes |
Potential separation digital inputs |
between the channels | No |
between the channels and the power supply of the electronics | No |
Potential separation digital outputs |
between the channels | No |
between the channels and the power supply of the electronics | No |
Isolation |
Isolation tested with | 1 500 V AC between PROFINET and electronics |
Degree and class of protection |
Degree of protection acc. to EN 60529 | IP20 |
Ambient conditions |
Ambient temperature during operation |
min. | -40 °C |
max. | 70 °C |
horizontal installation, min. | -40 °C |
horizontal installation, max. | 70 °C; Observe derating |
vertical installation, min. | -40 °C |
vertical installation, max. | 60 °C; Observe derating |
Ambient temperature during storage/transportation |
min. | -40 °C |
max. | 85 °C |
Relative humidity |
Operation, max. | 95 % |
Connection method |
Design of electrical connection | Connection plug |
Spur line |
Number of spur lines | 8 |
Type of cable | Type A |
Cable diameter, min. | 6 mm |
Cable diameter, max. | 12 mm |
Conductor cross-section, min. | 0.2 mm² |
Conductor cross-section, max. | 2.5 mm² |
Cable length, max. | 120 m |
total current output to field devices, max. | 320 mA |
Number of connectable field devices | 8 |
Current limitation per field device, max. | 40 mA |
No-load voltage, max. | 15.3 V |
short-circuit proof | Yes |
Short-circuit current (test current); max. | 8 mA |
intrinsically safe according to FISCO model | Yes |
Debounce logic | Yes |
Dimensions |
Width | 329 mm |
Height | 123 mm |
Depth | 74 mm |
Weights |
Weight, approx. | 580 g |