6GK1503-2CB00
PROFIBUS OLM/G11 V4.0

From SIEMENS

Product type designationPROFIBUS OLM/G11 V4.0
PROFIBUS OLM/G11 V4.0 optical Link module with 1 RS485 and 1 glass fiber-optic cable interface (2 BFOC sockets), with signaling contact and test port
Transmission rate
Transfer rate / with PROFIBUS9.6 kbit/s ... 12 Mbit/s
Transfer rate / with PROFIBUS PA45.45 kbit/s
Interfaces
Number of electrical/optical connections / for network components or terminal equipment / maximum2
Number of electrical connections
for network components or terminal equipment1
for measuring device1
for signaling contact1
for power supply1
for redundant voltage supply1
Type of electrical connection
for network components or terminal equipment9-pin Sub-D socket
for measuring device2-pole terminal block
for power supply and signaling contact5-pole terminal block
Number of optical interfaces / for fiber optic cable1
Design of the optical interface / for fiber optic cableBFOC port
Optical data
Damping ratio / of the FOC transmission link
for glass FOC with 50/125 µm / at 3 dB/km / maximum10 dB
for glass FOC with 62.5/125 µm / at 3.5 dB/km / maximum12 dB
propagation delay [bit]6.5 bit
Connectable optical power relative to 1 mW
for glass FOC with 50/125 µm / at 3 dB/km-16 dB
for glass FOC with 62.5/125 µm / at 3.5 dB/km-13 dB
Optical sensitivity relating to 1 mW
for glass FOC with 50/125 µm / at 3 dB/km-28 dB
for glass FOC with 62.5/125 µm / at 3.5 dB/km-28 dB
Wavelength
for glass FOC with 50/125 µm / compatible with interface / at 3 dB/km860 nm
for glass FOC with 62.5/125 µm / compatible with interface / at 3.5 dB/km860 nm
Wire length
for glass FOC with 50/125 µm / at 3 dB/km / maximum3 km
for glass FOC with 62.5/125 µm / at 3.5 dB/km / maximum3 km
Signal-Inputs/outputs
Operating voltage / of the signaling contacts / at DC / Rated value24 V
Operating current / of the signaling contacts / at DC / maximum0.1 A
Supply voltage, current consumption, power loss
Type of voltage / of the supply voltageDC
Supply voltage / at DC / Rated value24 V
Supply voltage / at DC18.8 ... 28.8 V
Product component / fusing at power supply inputYes
Consumed current / at DC / at 24 V / maximum0.2 A
Permitted ambient conditions
Ambient temperature
during operation0 ... 60 °C
during storage-40 ... +70 °C
during transport-40 ... +70 °C
Relative humidity / at 25 °C / without condensation / during operation / maximum95 %
Protection class IPIP40
Design, dimensions and weight
Designcompact
Width39.5 mm
Height112 mm
Depth74.5 mm
Net weight340 g
Mounting type
35 mm DIN rail mountingYes
wall mountingYes
Product functions / Redundancy
Product function / Ring redundancyYes
Standards, specifications, approvals
Standard
for FMFM3611: Class 1, Division 2, Group A, B, C, D / T4, Class 1, Zone 2, Group IIC, T4
for hazardous zoneEN 60079-0: 2006, EN60079-15: 2005, EN60079-28: 2007, II 3 (2) G Ex nA [opis] IIC T4 KEMA 09 ATEX 0173X
for safety / from CSA and ULUL 60950-1, CSA C22.2 Nr. 60950-1
for hazardous zone / from CSA and ULUL 1604 and UL 2279-15 (Hazardous Location), CSA C22.2 No. 213-M1987, Class 1 / Division 2 / Group A, B, C, D / T4, Class 1 / Zone 2 / Group IIC / T4
for emitted interferenceEN 61000-6-4 (Class A)
for interference immunityEN 61000-6-2
Certificate of suitabilityEN 61000-6-2, EN 61000-6-4
CE markingYes
C-TickYes
Marine classification association
American Bureau of Shipping Europe Ltd. (ABS)Yes
Bureau Veritas (BV)Yes
Det Norske Veritas (DNV)Yes
Germanische Lloyd (GL)Yes
Lloyds Register of Shipping (LRS)Yes
Nippon Kaiji Kyokai (NK)Yes

External links